Abstract

The three quantities are (1) residual fault current, (2) steady-state recovery voltage, and (3) natural frequency of transient recovery voltage. Loci of constant values of each of these, plotted in rectangular coordinates of degree of zero-sequence shunt compensation versus degree of positive-sequence shunt compensation, are straight lines. The assignment of sets of such constant values gives a family of straight lines. The first family, representing fault current, are parallel and have positive slope. The third family, representing natural frequencies are parallel and have negative slope. The second family, representing recovery voltage, has differing slopes but all lines pass through a common point at coordinates 1,1.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.