Abstract

The authors present measurements of the trapped charge in short samples of commercial XLPE (cross-linked polyethylene) insulated power cable. Charge injection was investigated for both AC and DC electric stressing of the samples, for various conditions of temperature and gaseous environment. The injected space charge was examined using three techniques: thermally stimulated discharge current (TSDC), field-assisted TSDC, and the thermal transient current method. These results are compared and the viability of the latter, nondestructive technique to monitor the process of aging in commercial cables is discussed. The presence of a space-charge peak at 60 degrees C in prestressed XLPE insulation is clearly seen using the TSDC method. Field-assisted TSDC illustrates strong ionic conduction at higher temperatures. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.