Abstract

This paper reports the results of an experimental study dealing with a commercial Rogowski coil current transducer (RCCT) in the presence of harmonic distortion. The RCCT was observed under two conditions: 1) sinusoidal excitation with frequencies from 50 to 750 Hz and 2) nonsinusoidal excitation using fundamental frequency and one harmonic, with adjustable amplitude and phase shift. The experimental results show only a weak dependence of the harmonic current ratio error and phase displacement on the amplitude and phase shift of the excitation harmonic. The phase displacement is also independent of the conductor position within the Rogowski coil window. An error compensation method, based on the frequency response, was implemented and tested with a distorted waveform. The compensation method allows one to obtain an improvement of the RCCT accuracy class from 1% and 1 <formula formulatype="inline" xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex Notation="TeX">$^{\circ}$</tex></formula> , in the case of a sinusoidal signal at mains frequency, to 0.05% and 0.05 <formula formulatype="inline" xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex Notation="TeX">$^{\circ}$</tex></formula> , both for the fundamental and the distorted signal harmonics.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.