Abstract

Reduced use of high global warming potential (GWP) hydrofluorocarbon (HFC) refrigerants is desired. However, many lower-GWP alternatives are flammable, some of higher flammability levels, or A3, and others of lower flammability (A2 or A2L). Safety standards for A2 and A3 flammable refrigerants, including the International Electrotechnical Commission (IEC) standard IEC 60335-2-40 calculate maximum flammable refrigerant charge limits using a fixed 4-minute leak time based on the time to leak 150 g of CO2 through a capillary tube. Actual refrigerant leak times depend on the equipment type, leak location, leak orifice diameter and equipment operation condition (on or off). Five systems were installed in test chambers with leak quantities and rates measured by tracking total system weight during the leak event. Among the major results were that almost all of the system charge was shown to escape the units, >80% within the first 10 minutes.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.