Abstract

This paper will suggest that the 1 cross orthogonal loop type sensor improves on the orthogonal loop form sensor-head, which is available a calibration of the linear birefringence, when a fiber optic current sensor was composed, An output characteristics of the 1 cross orthogonal loop form, a general closed loop form, the orthogonal loop form are compared by the IEC(International Electrotechnical Commission) 60044-8 standard, and the state of polarization is compared with three forms.<BR> As a result, when the closed loop form was changed to the orthogonal loop form, retardation decreased 15.3[%]. When the closed loop form was changed to the 1 cross orthogonal loop type, the retardation decreased 33.8[%]. As a result of the Faraday Effect measurement, the 1 cross orthogonal loop form has the highest output characteristic and the lowest error ratio. It met the 0.5 class of the IEC 60044-8 standard.<BR> Thus, in application of the lcross orthogonal loop form, the possibility to develop high reliability fiber optic current sensors that have a high output and stable error ratio rises is increased.