Abstract

Online partial discharge measurement in machines requires effective electrical noise suppression to reduce the risk of false indications of stator winding insulation problems. Many noise suppression techniques have been proposed and implemented over the years. This paper examines the method of suppressing noise using 3 phase synchronous (i.e. simultaneous) detection. Known noise pulses were recorded on three phases and they were contrasted with pulses from phase-to-ground PD in the stator slot or phase-to-phase PD between coils in the stator endwinding. Experiments indicated that interphasal PD produces strong pulses on 2 of the 3 phases. In contrast, phase-to-ground PD and noise caused by sparking in one phase of a generator output bus create a dominant pulse in one phase only. With all three types of situations, there may be significant cross-coupling to the other phase(s).

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.