Abstract

The flashover voltage with the backside electrode was lower than one without the backside electrode. Under μs pulse voltage application, we describe about characteristics of creeping discharge developed in narrow gap with the backside electrode. Using CCD camera and ultra-high speed camera, we observed the corona extension processes. As a result, the lowest flashover voltage was obtained in positive polarity of SF6 content D=3%. In corona extension obtained using ultra-high speed camera, the peculiar differences were observed on the corona extension process. The corona extension increased, and rapid flashover were observed in D=3%. Using CCD camera, the small corona were detected from backside electrode.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.