Abstract

Large cooking oil pool fires, occurring in industrial oil cookers, present a severe hazard to food processing plants due to their size and the large amount of hot oil involved. This paper reports a series of full-scale fire experiments conducted in a large industrial oil cooker mock-up. The characteristics of large cooking oil pool fires and the effect of oil depth and hood position in the oil cooker on fire growth were studied. The use of water mist for extinguishing large oil pool fires and their extinguishing performance under different discharge pressure and with different types of water mist systems were investigated. Experimental results showed that the cooking oil underwent a substantial expansion in volume during heating. The fires developed quickly once the oil auto-ignited. The fire growth rate was affected by the oil depth in the pan and the hood position in the oil cooker. The water mist fire suppression systems effectively extinguished large cooking oil fires and prevented them from re-igniting. Their extinguishing performance was determined by the type of water mist system, discharge pressure and hood position in the oil cooker.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.