Abstract

The article presents the results of the analysis of parameters describing electricity consumption in individual phases of the production cycle on a poultry farm. One full broiler rearing cycle on the farm was analyzed. Electrical parameters were tested during the broiler rearing process using a power quality analyzer with a measurement interval of 1 min. During the tests, the analyzer recorded the active and reactive power, phase and line voltage, power factor, and frequency. On the basis of collected data, original indicators describing electricity consumption per chicken wkA, wkQ, and per unit area wiA, wiQ were determined. The regression curves of active and reactive power consumption in particular stages of the cycle were also determined, and the minimum and maximum values of active and reactive power consumption were determined. The accomplished research can be used in planning electricity demand in energy-self-sufficient areas. The presented original indicators can be used to determine power demand on broiler farms, depending on the planned production volume or size of farm buildings.