Abstract

Results of tests and research are given covering EHV station post insulators from 1,300 BIL (basic insulation level) to 2,100 BIL, including flashover and withstand on 60 cycle wet and dry, impulse and switching surge, wet and dry tests. As of today there is no information such as this in the literature. Since several United States and Canadian systems are now in the midst of 500and 700-kv substation design, the information should be timely. Some data are inconclusive and will have to be verified or varied by additional testing. Other data are presented to show trends rather than final results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.