Abstract
The paper extends the theoretical study of diode-bridge-loaded synchronous generators without damper windings to loads with commutation angles equal to or greater than 60° (modes 2 and 3). The equations necessary to establish the performance in these operating modes, and a simple method of establishing the boundaries between the modes, are given. Constant flux linkages are assumed. Experimental results from tests on a 5 kVA laboratory generator have been used to check the computed theoretical results obtained by using the published equations. A larger, turbogenerator exciter has been used to illustrate the theoretical difference between operation in mode 1 and mode 2.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Similar Papers
More From: Proceedings of the Institution of Electrical Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.