Abstract

Sheath current can cause sheath loss and reduce the permissible current of a power cable transmission system. High sheath current is usually caused by mixed cable burying formation, different length between sections, poor connection of the bonding leads, and connection of distribution cable onto transmission systems. This paper analyses the characteristics of sheath circulating current at various conditions and presents a useful method to reduce it in a mixed burying formation system. It can effectively reduce the current by up to 90%. The method is validated by practical measurements and simulations using ATP, and has been implemented in actual systems. In addition, a special equipment is designed to measure and analyze the sheath circulating current. It can measure and analyze nine currents at a same time.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.