Abstract
AbstractRegardless of material regulations at the supply source or post-construction quality inspection systems, certain levels of model management systems have been developed. However, in the hospital waiting room, the measured formaldehyde concentration in the air reached 0.99 ppm, which is 12 times higher than that of the standard value.The formaldehyde emission rates measured in the building materials of the private housings or hospital waiting room ranged from 158 to 238 μg/m2∙h, which exceed both the ABSL and BSMI standards. Moreover, the decoration locations, construction staff, and construction behaviors varied despite their claims of using low formaldehyde-emitting materials.This study compiled the current objectives and regulations established by various supervising authorities and implemented a supporting management system in material grading, amount of material usage, ventilation path control, and ventilation effectiveness for facilitating the promotion of healthy indoor air quality, thereby enhancing public health.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.