Abstract

The recent aim of the earthquake resistant design is not only to protect life in very severe earthquakes, but also to use the buildings again after the earthquakes with small repair cost. A building system consisted with “coupled shear core walls with damper”, CFT (Concrete Filled Steel Tube) columns, and flat plate slabs is one of the buildings having an ability of such demand. As floor load should be supported even in the large deformation at the CFT column-flat plate connection, it is required to avoid punching shear failure. To evaluate the vertical load resistance capacity of the newly designed CFT column-flat plate connection, experimental studies were carried out. The vertical force resisting mechanism of the joint zone is investigated and calculation can be made with fairly good accuracy by regarding a region with a shear force resisting vertical member as a truss system and regarding a region without such a member as an arch system. Vertical strength also can be calculated conservatively as a lower value of a simplified punching shear strength formula conforming to the ACI standard and a flexural yield strength value.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.