Abstract

In November 1981, a waterborne giardiasis outbreak occurred within the Highlands Water and Sanitation District in Colorado. Although the immediate cause of the outbreak was reduced chlorine contact time because of a pump failure, numerous design and operational deficiencies existed at the plant. Lack of chemical pretreatment, improper backwashing procedures, poor application of raw water to the filter, and failure to monitor plant conditions all contributed to the outbreak. Turbidity and bacteriological records did not indicate any problems, confirming the crucial role of proper design, installation, and operation of the multibarrier technique in preventing waterborne giardiasis outbreaks.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.