Abstract
It has been known that FAC, LDIE, cavitation and flashing are the damage mechanisms that can cause the pipe thickness of the secondary system of nuclear power plants thinner. Severe wall thinning was found in the MSR drain pipes at a Korean nuclear power plant a decade ago, and all the affected pipes were replaced with low alloy steel with higher chromium contents. Therefore, this study was conducted to reduce the possibility of similar thinning cases that may occur in the future by identifying the exact cause of thinning. ToSPACE and FLUENT codes and theoretical evaluation method were applied to analyze the causes of thinning. ToSPACE and FLUENT analyses and theoretical evaluation including all the operating conditions show a relatively large pressure drop and a pressure lower than the saturated vapor pressure in common at the end of the pipe entering the condenser. This means that flashing occurs at the end of the pipe under all operating conditions, and the effect can be greater than that of other parts. As a result, since severe wall thinning occurred at the end of the pipeline entering the condenser, it was evaluated that flashing by the high-velocity two-phase fluid was the direct cause of the wall thinning in the MSR drain pipes. The results of this study will contribute to establishing appropriate countermeasures in the event of pipe wall thinning in the future.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.