Abstract

Computational fluid dynamics (CFD) modeling and full-scale tracer tests (using barium or fluoride) were used to determine the baffle factors of clearwells at three Canadian water treatment facilities (two in Ottawa, Ontario, and one in Peterborough, Ontario). A variety of clearwell baffling configurations and a range of flow rates (35 to 257 MLD) were considered. Two-dimensional CFD modeling (no depth dimension) was conducted using commercially available software (Fluent 6.0®). Virtual particle tracking allowed simulation of the residence time distribution for each clearwell configuration and flow rate condition. The baffle factors (t10/θ) derived from the CFD modeling closely matched the values obtained from full-scale tracer testing (<10% difference in most cases). The results of the study suggest that CFD modeling can be a reliable alternative to tracer testing for determining clearwell residence times and can thereby provide improved estimates of chemical disinfection performance and disinfection by-product formation. Key words: computational fluid dynamics, tracer, clearwell, baffle factor, barium, fluoride, disinfection, drinking water.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call