Abstract

It is an effective measure for power enterprises to improve the voltage level of the system by raising and lowering the tap position of the main transformer. For the parallel operation of the main transformer, the whole process of adjusting the tap must strictly meet the conditions of parallel operation. Aiming at a case of backup protection action of main transformer caused by improper implementation of voltage regulation measures, this paper analyzes the uneven load distribution and increase of reactive power loss caused by improper adjustment of tap, and the analysis results are verified by PSCAD.