Abstract

This article investigates the operation of cascaded H-bridge (CHB) based static synchronous compensator (STATCOM) after failure in its submodules (SMs). Once a switch fails, the corresponding faulty SM is bypassed. In the post-fault operation, a zero-sequence voltage (ZSV) is injected to the converter phases to generate the maximum possible line-to-line voltage. Using a clamping technique, the fundamental component of injected ZSV (FZSV) is minimized according to the operating point of CHB STATCOM. But, FZSV leads to unequal flow of active power into the converter phases. In the proposed method, negative-sequence current is controlled to manage the active power flow within CHB phases. By doing this, the effect of FZSV on active power of CHB phases is compensated and the voltages of capacitors are kept balanced. This method ensures the continuous operation of CHB STATCOM with the minimum over-design and guarantees the voltage balance of capacitors after a failure. The presented simulation and experimental results validate the feasibility and effectiveness of the proposed method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.