Abstract

The objective of this paper is to investigate an impact of the inrush current on the prestrike and restrike characteristics of vacuum interrupters (VIs) during capacitive current switching duty. Eleven 7.2 kV VIs are used. Their contact parameters are contact gap 4 mm and contact material CuCr25 (25%weight of Cr). A series of 80 CO operations are executed for each test VI. The amplitude of inrush current Iinrush (3800 Hz) is set to 0 kA, 2 kA, 5 kA and 10 kA, respectively. The switching current is less than 1 A rms. The (1-cosωt) shape of the recovery voltage with a peak of 15 kV is applied to the test VI. The experimental results show that the prestrike and restrike phenomena are significantly influenced by the contact surface conditions damaged by the inrush current. The cumulative probability of the prestrike gap dpre follows a 3- parameter Weibull distribution. When Iinrush increases from 2 kA to 5 kA, the prestrike gap increases accordingly. The 10% dpre increases from 0.5 mm to 0.7 mm. The 50% dpre increases from 0.7 mm to 1.0 mm. The 90% dpre increases from 1.0 mm to 1.5 mm. The scale in the Weibull distribution, which can describe the scattering of dpre, is 0.2 mm and 0.6 mm in the case of Iinrush = 2 kA and Iinrush = 5 kA, respectively. It is found that the occurrence frequency of the inrush current interruption increases from 37.9% to 68.3% with the increase of Iinrush from 2 kA to 5 kA. Moreover, the inrush current also has an impact on the restrike types, which are classified into three types according to the waveform features. The average restrike probability increases from 4.6% to 17.9% and further to 30.4% with the increase of the inrush current from 0 kA to 2 kA and 5 kA, respectively. In addition, the higher the inrush current, the restrike tends to occur earlier during the recovery voltage period.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call