Abstract

This part of the paper presents calculated results of the program for eddy current losses and circulating currents and losses of several large power transformers. In order to demonstrate the improved accuracy and the new and valuable information provided by the program, the 3D results are compared to 2D results, results of approximate classical formulas of losses, and finally test results on several commercial transformers. The results of a study on the effect of braze splitting and transposition on circulating currents using the 3D loss program are also presented.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.