Abstract

Point-on-wave (POW) is a single-event characteristic of voltage dips, influencing the performance of sensitive equipment, such as AC contactor and wind turbines. However, definition and calculation of POW are unsolved issues. The existing definition of POW is for single-phase dips; it does not consider three-phase dips. Moreover, existing POW calculation methods are inaccurate. This paper proposes a definition of POW as a single-event characteristic for three-phase voltage dips. Then, it proposes a POW calculation method based on space vector, including POW detection and angle calculation. The proposed method is based on the ellipse characteristics during the dip-stage and non-dip stage. The proposed method does not depend on zero crossing for angle reference. To verify the performance of the proposed method, a power-system simulation model is built to generate voltage dips with different origin. Furthermore, the accuracy of the proposed method is verified by 425 sets measured voltage dips, and compared with the published methods.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.