Abstract

Sudden three-phase short-circuit current of a turbine generator was calculated by a three-dimensional magnetic field analysis. That analysis takes into account the rotation, magnetic saturation, and eddy current at a rotor part. To compare test results and calculated results, a method was proposed for short-circuit phase estimation at sudden three-phase short-circuit test by line voltage waveform of the test results. The calculated results of short-circuit current waveform are in good agreement with the test results. © 2005 Wiley Periodicals, Inc. Electr Eng Jpn, 153(1): 54–62, 2005; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.20110