Abstract

Sudden three-phase short-circuit current of a turbine generator was calculated by a three-dimensional magnetic field analysis. That analysis takes into account the rotation, magnetic saturation, and eddy current at a rotor part. To compare test results and calculated results, a method was proposed for short-circuit phase estimation at sudden three-phase short-circuit test by line voltage waveform of the test results. The calculated results of short-circuit current waveform are in good agreement with the test results. © 2005 Wiley Periodicals, Inc. Electr Eng Jpn, 153(1): 54–62, 2005; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.20110

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.