Abstract
This paper presents the 3-D CFD calculation results of the pressure rise due to the High Energy Arcing Faults (HEAFs) in the metal-clad switchgears. The calculations were performed considering the came-off of the roof panel that was observed in the arc tests. The calculated pressure development approximately agreed with the measured one. Furthermore, the energy of hot gases exhausted from the broken roof panel was calculated to investigate the thermal effect of hot gases.