Abstract

In order to investigate the feasibility of using new transmission line configurations with nonparallel conductors, for managing magnetic field in critical areas, techniques are needed to assess the effects of different three-dimensional line arrangements on other important design parameters. A new method for calculation of electric field and corona-generated audible noise from nonparallel conductors is described and implemented as a computer tool. This method uses linearly varying line charges to simulate charge distribution along the axial direction of the transmission line. New algorithms are developed for calculating electric field and audible noise due to nonuniform line charges and illustrated by examples of low magnetic field transmission line designs.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.