Abstract

In view of the fact that the influence of positive and negative sequence decomposition, which is widely used in positive and negative sequence decoupling control in control system, on the fault current calculation process is not deeply considered in the existing transient analysis methods of permanent magnet direct-drive wind farm short circuit current, this paper proposes a transient short circuit current calculation model that takes into account positive and negative sequence decomposition. The influence of the transient characteristics of positive and negative sequence decomposition on the control system is studied, and the mechanism of its action on the transient change of short circuit current is revealed. The positive and negative sequence decoupling processes of the circuit equation are modified, and the characteristics of the coupling equation are analyzed. The difference in the converter output voltage between the circuit equation and the control equation and the depth of its influence on the calculation process is revealed. On the basis of quantifying the difference at the converter output voltage, the circuit equation and the control equation are combined to form a short-circuit current calculation model with positive and negative sequence decomposition, which accurately characterizes the transient characteristics of fault current under different voltage drops and effectively improves the accuracy of the calculation results.