Abstract
For DC line protection of the Hokkaido-Honshu HVDC Link, a submarine cable fault detection system was developed. In this system, a DC line fault is declared when DC currents at both cable heads change mutually in the reverse direction. Combining this detection system with a current difference detection system which operates for any fault occurring on the high voltage DC transmission line, the high voltage DC line protection system is composed. Through the simulator tests and five-year field experience, the detection system has been verified to be satisfactory.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.