Aiming at the problem of low positioning accuracy caused by modal aliasing and noise interference in DC cable fault location analysis of a VSC-HVDC system, a double-ended fault location method for flexible DC cables based on improved local mean decomposition is proposed. Firstly, the local mean decomposition (LMD) is used to decompose the six-mode voltage signal to obtain the product function (PF) component; then, to overcome the problem that the instantaneous frequency function of the LMD is limited by the extreme value, the Hilbert transform is performed on the PF1 to obtain the instantaneous frequency curve, and the arrival time of the voltage traveling wave head is determined from the mutation information. Finally, the fault distance is obtained by using the principle of double-ended traveling wave fault location. Different fault conditions are simulated, analyzed, and compared with wavelet transform and Hilbert–Huang transform. The results show that the proposed method has a positioning error within 1%, and it is less affected by interference noise and transition resistance.