Abstract

DC power systems, like the ones proposed for use in future naval electric ships, can be made more reliable by using multiple buses for redundancy. Multiple buses provide multiple configuration options for supplying power to the load. Diode OR'ing with auctioneering diodes is perhaps the most common method to connect a load to multiple buses. Although the diode action is automatic and fault-tolerant, it results in ill-defined bus currents when the bus voltages are similar and the potential for uncontrolled switching in a faulted high-impedance system. Active switching and bus converters with auctioneering diodes are control techniques that overcome these limitations by providing full control over the bus selection process. Using local information in the form of the bus voltage, these techniques do not rely on a centralized controller, which improves system reliability. Dwell time is shown as a technique to stabilize the state-dependent switching.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.