Abstract

A large number of nonlinear loads and distributed energy sources are connected to the power system, leading to the generation of broadband dynamic signals including inter-harmonics and decaying DC (DDC) components. This causes deterioration of power quality and errors during power measurement. Therefore, effective phasor estimation methods are needed for accurate monitoring and effective analysis of harmonics and interharmonic phasors. For this purpose, an algorithm is proposed in this paper that is implemented in two parts. The first part is based on the least square method in order to obtain accurate DDC component. In the second part, a Taylor–Fourier model of broadband dynamic harmonic phasor is established. The regularization optimization problem of the sparse acquisition model is solved by harmonic vector estimation method. Finally, the piecewise Split-Bregman Iterative (SBI) framework is used to obtain the estimated value of the harmonic phasor measurement and to realize the reconstruction of the original signal. Through simulation and performance test, the proposed algorithm significantly improves the accuracy of the phasor measurement and estimation, and can provide a reliable theoretical basis for the PMU measurement.