Abstract

Here, breakdown tests of cap-and-pin glass insulators with arcing horns, conducted at two different HV labs, are presented. Since only volt-time curves are measured, a curve-fitting approach to determine leader progression model parameters is taken, which involves modelling of the impulse generator in detail and inclusion of the Motoyama model to simulate the breakdown. Furthermore, a comparison of the breakdown simulation results with LPM parameters for a pure air gap and the measurements is accomplished. Finally, a curve-fitting procedure is developed to fit the resulting volt-time curves from simulations to the measurements.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call