Abstract
Reliable and comprehensive measurement data from large-scale fire tests are needed for validation of computer fire models, but is subject to various uncertainties, including radiation errors in temperature measurement. Here, a simple method for post-processing thermocouple data is demonstrated, within the scope of a series of large-scale fire tests, in order to establish a well characterised dataset of physical parameter values which can be used with confidence in model validation. Sensitivity analyses reveal the relationship of the correction uncertainty to the assumed optical properties and the thermocouple distribution. The analysis also facilitates the generation of maps of an equivalent radiative flux within the fire compartment, a quantity which usefully characterises the thermal exposures of structural components. Large spatial and temporal variations are found, with regions of most severe exposures not being collocated with the peak gas temperatures; this picture is at variance with the assumption of uniform heating conditions often adopted for post-flashover fires.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.