Abstract

Parallel ac-dc reconfigurable link technology can find interesting applications in medium voltage power distribution. A given system can operate in different configurations while maintaining equivalent capacity during (n-1) contingencies. It is proved that within the defined operating boundaries, a parallel ac-dc configuration has higher efficiency as compared to pure ac or pure dc power delivery. Using sensitivity analysis, the variations in these efficiency boundaries with power demand, power factor, grid voltages, link lengths, conductor areas and converter efficiency is described. It is shown that parallel ac-dc system can have smaller payback time as compared to a purely dc power transmission for the same capacity due to lower investment cost in converter station and superior efficiency. As compared to a purely ac system, the payback of a refurbished parallel acdc configuration can be less than 5 years for a 10 km, 10 kV distribution link within the specified assumptions and operating conditions.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.