Abstract

In this study, the effect of carbon nanotubes (CNTs) on nucleate boiling heat transfer is investigated. Two halocarbon refrigerants of R123 and R134a for building chillers were used as working fluids and 1.0 vol.% of CNTs was added to them to examine the heat transfer enhancement with CNTs. The experimental apparatus was composed of a stainless steel vessel and a 152.0 mm long plain horizontal tube of 19.0 mm outside diameter heated by a cartridge heater. All data were obtained at the pool temperature of 7 °C in the heat flux range of 10–80 kW m −2. Test results showed that CNTs increase nucleate boiling heat transfer coefficients for these refrigerants. Especially, large enhancement up to 36.6% was observed at low heat fluxes of less than 30 kW m −2. With increasing heat flux, however, the enhancement was suppressed due to vigorous bubble generation. Fouling on the heat transfer surface was not observed during the course of this study. Optimum dispersion of CNTs should be examined for their commercial application to enhance nucleate boiling heat transfer in building air-conditioning applications.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.