Abstract
A novel magnetic-controlled switcher type fault current limiter (FCL) for high voltage electric network is presented. The current limiting principle of the FCL and the bias current influence on the characteristic of the FCL are discussed. The experiments on the 220 V/50 A test model show that the FCL can limit the fault current swiftly and effectively. Under the normal state, the bias current adjustment can change the FCL voltage loss; under the fault state, the steady fault current can be easily adjusted to the preset level by bias current regulating. The experimental result is in accordance with the principle analysis and the FCL has the advantages of flexible control strategy and simple and reliable structure.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.