Abstract

Unreinforced masonry (URM) buildings perform poorly under seismic forces and have been identified as the main cause of loss of life in recent earthquakes. Many of these structures fail in out-of-plane bending due to the lack of reinforcement. In this study, the experimental results from three half-scale unreinforced brick walls retrofitted with vertical composite strips are presented. The specimens were subjected to cyclic out-of-plane loading. Five reinforcement ratios and two different glass fabric composite densities were investigated. The mode of failure is controlled by tensile failure when wider and lighter composite fabrics are used and by delamination when stronger ones are used. The tested specimens were capable of supporting a lateral load up to 32 times the weight of the wall. A deflection as much as 2% of the wall height was measured. Although both URM walls and composite strips behave in a brittle manner, the combination resulted in a system capable of dissipating some energy. Retrofitting UR...

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.