Abstract
A sparsely instrumented 55-story building in Osaka, Japan, had recorded unprecedented, severe, and long-duration, long-period resonating responses during the 11 March 2011 M9.0 Tohoku earthquake that occurred at 767 km distance. Thereafter, studies of the records resulted in the implementation of a significant retrofit design, comprising dampers and buckling restrained braces (BRBs). The responses of the retrofitted building were also recorded during the 24 April 2016 M7.3 Kumamoto earthquake that occurred at 478 km. The earthquake and on-demand acquired ambient response data are analyzed in this study to assess the impact of this rare, retrofitted and instrumented tall building subjected to long period strong shaking from events originating at far distances. As expected, the fundamental frequency and critical damping ratio of the building increased, albeit small, after the retrofit as compared to before the retrofit. Increase of damping percentage is a positive finding and indicates that even larger percentages may be attained under shaking stronger than the 2016 event. The records indicate that the building still experiences significant resonance, torsion, as well as a beating effect.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.