Abstract
The foundation was an important part of the structure. In foundation design, it was necessary to considered the foundation condition to be built must be able to support the load up to the allowable capacity. To determine a safe foundation requires analysis using several of static methods. This research was conducted to obtain a critical bearing capacity so that it can be used to determine a very safe foundation. In this study, analysis of the bearing capacity of pile foundations was calculate using the method of Briaud et al. (1985), Meyerhof (1956), Decourt (1982), Shioi & Fukui (1982) based on SPT N-value obtained from the field at borehole 1 (BH-01) and borehole 2 (BH-02). Based on the analytical result of the bearing capacity calculation of a pile foundation with a diameter of 0.35m on depth of 24m, The lowest of bearing capacity (critical value) used to determine the number of piles is the method of Briaud et al. (1985) was 90.55 tons at borehole 1 and 87.06 tons at borehole 2. This value was use as a guideline for determining the number of pile foundations used in reservoir construction design.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.