This study presents the control of distribution static compensator (DSTATCOM) using band-dependent variable step size (BD-VSS) individual weighting factor with sign error based adaptive filter for power quality improvement in a weak distribution grid. Here, the proposed algorithm is used for estimation of fundamental active weight components from the distorted load currents in order to generate the reference grid currents to mitigate the grid currents power quality issues. This new control algorithm is proposed for fast and accurate estimation of active weight components with low steady-state error, without dynamic oscillation at fast convergence speed. Moreover, the frequency locked loop-double self-tuning second-order generalised integrator based voltage filter is used to extract the positive sequence voltages of the distorted grid voltages for estimating the harmonics, and noise-free voltage unit templates. Therefore, the DSTATCOM with the proposed control algorithm is capable of mitigating the harmonic currents, providing reactive power compensation and operating at unity power factor in a weak distribution grid. Test results demonstrate the viability and robustness of the proposed control algorithm under balanced and unbalanced non-linear load conditions.