Abstract

An experimental investigation was conducted to evaluate bar size factors used for the calculation of required lap splice lengths according to US and Canadian codes for concrete block masonry walls subjected to out-of-plane loads. Wall splice specimens were constructed in running bond with all cells fully grouted, and were tested under monotonically increasing four-point loading. Specimens were longitudinally reinforced with either No. 15, 20, or 25 reinforcing bars with varying lap splice lengths that were sufficiently short to ensure that a bond failure would precede a failure in flexure. Modifications to the bar size factors included in both codes were derived from the resulting test data. The evaluation of the test data shows that decreases to lap splice lengths could be considered for walls subjected to out-of-plane loads, which would facilitate construction.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.