Abstract
The doubly-fed induction generator (DFIG) system currently occupies close to 50% of the wind energy market. The vector control is the proven and state-of-the-art solution for its back-to-back power converters by using the dual-loop controller design: the inner current and the outer voltage/power. This paper focuses on the modelling of power converters and the parameters design of proportional-integral controller. According to the Bode plots, the relationship among the switching frequency, inner loop bandwidth, and outer loop bandwidth can be found. At least one-tenth difference between them is necessary for the sake of either the switching harmonic mitigation or the fully decouple of the dual loops. The procedure to design bandwidth for the grid-side converter and the rotor-side converter is thoroughly addressed and explained on a real-scale 2 MW and a down-scaled 7.5 kW DFIG systems. On the basis of the relationship between the controller bandwidth and the rise time, the theoretically designed bandwidth is able to be verified in both the simulation and the experiment.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.