The number of bacteria in air, before filtration with five different easily available filters in the low positive-pressure type of airconditioning system of the Winnipeg General Hospital, was between 3 and 4/cu. ft., and after filtration between 1 and 2/cu. ft. with all types of filters. Cl. welchii contributed about 1% and Staph. pyogenes about 0.1% of this total. Sampling the exhaust air from an operating room during an operation showed that the bacterial count fluctuated with the degree of activity in the room and was from two to 10 times as high as in the air delivered to the room.Atlhough every reasonable attempt should be made to diminish the bacterial count of air in hospitals, if much energy and money is to be spent it would probably be wiser to investigate sources of hospital infection other than the type of air-conditioning system described in this report.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.