The six-phase transmission can improve the power transmission density of the transmission lines effectively, and save line corridor. To save the problem that the sensitivity of the traditional transformer backup protection is low in six-phase transmission system, a backup protection for six-phase transformer was proposed. An over-current protection criterion is proposed for interphase short circuit and opposite zero sequence over-current protection criterion is proposed for ground faults, based on the six-sequence components relationship, and the existence of six-sequence components in different fault types. Theoretical analysis and EMTDC simulation experiments prove that the scheme is feasible.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.