Abstract

Series compensation poses serious challenges to the protection schemes of transmission lines (TLs). Moreover, with the penetration of distributed generation (DG), the conventional protection schemes fail to detect the fault and identify the faulty phase as the backfeed currents from the DG units mask the faulty phase. This work presents an algorithm for the protection of series-compensated TLs (SCTL) integrated with wind farms. The algorithm uses the phase difference between the positive sequence currents at the two ends of the TL to discriminate internal and external faults. The faulty phase for internal fault is identified from the difference in complex power at the two ends of the TL. Extensive simulations with several fault and system parameters assess the reliability and applicability of this technique.