Abstract
The study investigated the effect of the improved partial load COP of adsorption chillers on the cogeneration system in an office building. The partial load COP of the adsorption chiller was maximized by optimizing the cycle time. The COP of the adsorption chiller was increased with smaller partial load ratios by the extended cycle time. The performance of the cogeneration system with an adsorption chiller was analyzed by simulation, and the energy saving ratio of the system was presented. The energy saving ratio was compared with that by the cogeneration system with an absorption chiller. The results showed that the adsorption chiller was advantageous given that the adsorption chiller had the same rated COP value as the absorption chiller.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: The Proceedings of the National Symposium on Power and Energy Systems
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.