Abstract

Abstract Autotuning based on relay feedback tests have received a great deal of attention recently. The relay feedback tests fail to generate sustained oscillation in some cases. For systems with RHP poles and/or zeros, incorrect autotune identification procedure may give erroneous information and unstable limit cycle. Frequency domain analyses provide a criteria for prediction of the existence of stable limit cycle. Furthermore, a procedure is given to ensure the success of a relay feedback test. The analyses and procedure are illustrated through open loop stable and unstable systems. Results show that, except for some rare occasion, successful relay feedback experiments can be obtained following the proposed procedure.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.