Abstract
Traditional grounding method is hard to handle increasing capacitive grounding current in single-phase arcing faults due to the development of distribution systems. Therefore, automatic suppression strategy of single-phase arcing fault is proposed and simulation of arcing fault and its automatic suppression is realized in this paper. An improved zero sequence parameters measurement (IZSPM), injecting a current which contains three frequency components into secondary side of single-phase transformer to measure realtime zero sequence parameters, was proposed and verified in EMTP-ATP. In order to realize inductance tuning, fixed Petersen coil in parallel with an adjustable reactor was employed in this paper. The automatic suppression system, proposed in this paper, is convenient and possess rapid response.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.