Abstract

Automatic Generation Control (AGC) problem has been one of the major subjects in electric power system design/operation and is becoming much more significant today in accordance with increasing size, changing structure and complexity of interconnected power systems. In practice, AGC systems use simple proportional-integral (PI) controllers. However, since the PI controller parameters are usually tuned based on classical or trial-and-error approaches, they are incapable of obtaining good dynamical performance for a wide range of operating conditions and various load changes scenarios in a multi-area power system. In this paper, in order to design a robust PI controller for the AGC in a multi-area power system, first the problem is formulated as an Hinf static output feedback control problem, and then it is solved using a developed iterative linear matrix inequalities algorithm to get an optimal performance index. A three control area power system example with a wide range of load changes is given to illustrate the proposed approach and the results are compared with Hinf dynamic output feedback control design.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.