Abstract

This paper describes an automatic fault location technique for permanent faults in underground LV distribution networks (ULVDNs). It uses signals from an existing time domain reflectometry (TDR) instrument. It pre-processes TDR signals to eliminate reflections due to single-phase tee-offs, and to locate 3-phase open or short circuit faults and also uses adaptive filtering to compare the TDR signals to locate faults. In essence, the procedure minimizes the interpretation skill required from a user of a typical TDR based fault location instrument. The relative performance of the system is demonstrated using real field data.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.